Strona 1 - MODEL IMY INSTRUCTION MANUAL

THE APOLLO INTELLIGENT METER SERIESMODEL IMY INSTRUCTION MANUALimhCVR.QXD 3/8/02 10:12 AM Page 1

Strona 2 - INTRODUCTION

MODULE #1 - PROGRAM THERMISTOR TYPE, TEMPERATURE SCALE (F OR C)AND DECIMAL POINT POSITIONSelect the desired Thermistor type by pressing the “UP” or “D

Strona 3 - Table of Contents

MODULE #3 - PROGRAM FUNCTIONS ACCESSIBLE W/ FRONT PANEL LOCKOUTThis programming module programs what is accessible through the frontpanel when the PGM

Strona 4

TEMPERATURE OFFSET VALUE =If the Integrator/Totalizer/Peak/Valley/Temperature Offset option isinstalled, this selects whether the programmed offset va

Strona 5 - SAFETY INFORMATION

MODULE #4 - PROGRAM DIGITAL FILTER AND REMOTE INPUTPROGRAM DIGITAL FILTERINGIf the displayed process signal is difficult to read due to small processv

Strona 6

PROGRAM FUNCTION OF E1-CON AND OPTIONAL E2-CON(Cont’d)“9” - If the alarm option is installed, a low level resets a latched orunlatched alarm into its

Strona 7 - BLOCK DIAGRAM

MODULE #5 - PROGRAM INTEGRATOR/TOTALIZERProgramming for the integrator/totalizer consists of four programmingsteps: totalizer decimal point position,

Strona 8 - PROGRAMMING THE IMY

MODULE #6 - PROGRAM ALARM/SETPOINTIf the alarm option is installed, this module is used to configure theoperation of the alarms to a variety of combin

Strona 9 - request

ALARM #2 ASSIGNMENT TO INPUT OR INTEGRATOR/TOTALIZERAlarm #2 may be programmed to activate on either the input or theintegrator/totalizer value. If th

Strona 10 - AND DECIMAL POINT POSITION

MODULE #7 - PROGRAM SERIAL COMMUNICATIONSSeveral programmable parameters must be programmed before serialcommunication can occur.BAUD RATESelect one o

Strona 11

MODULE #8 - PROGRAM RE-TRANSMITTED ANALOG OUTPUTThis programming module allows digital scaling of the 4 to 20 mA or 0 to10 VDC analog output. The type

Strona 12 - ENTER OFFSET VALUE =

INTRODUCTIONThe Intelligent Meter for Thermistor Inputs (IMY) is another unit in our multi-purpose series of industrial control products that are fiel

Strona 13 - PROGRAM DIGITAL FILTERING

MODULE #9 - SERVICE OPERATIONSThe indicator has been fully calibrated at the factory. If the unit appears tobe indicating incorrectly or inaccurately,

Strona 14 - (Cont’d)

OPERATING THE IMYAfter completing all set-up operations, the unit is ready to install andoperate. After power is applied, a display test consisting of

Strona 15

FACTORY CONFIGURATIONThe following chart lists the programming of the unit when shipped from thefactory. (In Program Module #9, Code 66 will restore t

Strona 16

PROGRAMMING EXAMPLEAs an example of a programming sequence, the following values, gained froma temperature-time monitoring application, are programmed

Strona 17

TEMPERATURE MONITORING EXAMPLEAn IMY is installed as a monitoring device and back-upcontroller for a freezer storage facility. Normally, thefreezer te

Strona 18 - PRINT REQUEST FUNCTION

INTEGRATOR / TOTALIZER / PEAK / VALLEY / TEMPERATURE OFFSET (Optional)INTEGRATOR/TOTALIZERThe integrator/totalizer option simply adds input readings t

Strona 19 - ANALOG OUTPUT SOURCE

OFFSET AND SLOPE DISPLAY TEMPERATURE (Cont’d)SET-UP:“Pro 2” ... “SLOPE” - 1.0638“OFFSEt” - -5.3This feature allows the operator to manipulate the di

Strona 20

S.F . =110x (3600RR)Rx10110 28800 10(8 Hours x 3600)S.F. = 1x.125S.F. = .125“Pro 5”...“dECPNt” - 0.0“tbASE ” - 2“SCLFAC” - .125“Lo-cut ” - 0.0R This

Strona 21 - OPERATING THE IMY

ALARMS (Optional)The alarm option consists of an additional printed circuit board with nineterminals. Six of these terminals are the two Form-C relays

Strona 22 - FACTORY CONFIGURATION

20 mA CURRENT LOOP SERIAL COMMUNICATIONS (Optional)GENERAL DESCRIPTIONThe serial communication option is a half-duplex, two-way, 20 mA loopthat can co

Strona 23 - PROGRAMMING EXAMPLE

Table of ContentsSAFETY INFORMATION ······························································3Safety Summary ····································

Strona 24

SENDING COMMANDS TO THE IMYWhen sending commands to the unit a command string must beconstructed. The command string may consist of command codes, val

Strona 25 - PEAK/VALLEY

If illegal commands or characters are sent to the IM, an asterisk (*) must besent to clear the input buffer. The IM will not respond to an illegal ori

Strona 26 - INTEGRATOR/TOTALIZER SET-UP

RECEIVING DATA FROM THE IMYData is transmitted from the indicator whenever a “T” or “P” command isreceived via serial communications or a remote input

Strona 27

SERIAL COMMUNICATIONS EXAMPLESCONNECTING TO AN RLC PRINTERThe drawing shows the indicator with the 20 mA Serial CommunicationOption set-up with an RLC

Strona 28 - ALARMS (Optional)

-32-PROCESS CONTROLLING SYSTEMSix Model IMYs with Serial Communication Optionare used to monitor and control the temperature of 6ovens at a large bake

Strona 29 - COMMUNICATION FORMAT

RE-TRANSMITTED ANALOG OUTPUT (Optional)The re-transmitted analog output option transmits a digitallyprogrammable 4 to 20 mA or 0 to 10 VDC signal to d

Strona 30 - COMMAND STRING EXAMPLES

ANALOG OUTPUT CALIBRATIONAlthough the analog output has been calibrated at the factory, zero andspan adjustments are provided to compensate for small

Strona 31

APPENDIX “A” - INSTALLATION & CONNECTIONSINSTALLATION ENVIRONMENTThe unit should be installed in a location that does not exceed the maximumoperat

Strona 32 - SERIAL TERMINAL DESCRIPTIONS

EMC INSTALLATION GUIDELINESAlthough this unit is designed with a high degree of immunity toElectroMagnetic Interference (EMI), proper installation and

Strona 33 - CONNECTING TO AN RLC PRINTER

WIRING CONNECTIONSAfter the unit has been mechanically mounted, it is ready to be wired. Allconductors should meet voltage and current ratings for eac

Strona 34 - PROCESS CONTROLLING SYSTEM

Command String Examples ·························································28Receiving Data from the IMY ·······································

Strona 35

APPENDIX “B” - SPECIFICATIONS AND DIMENSIONS1. DISPLAY: 4-digit with F/C indication, 0.56" (14.2 mm) high LED, minussign displayed for negative t

Strona 36 - ANALOG OUTPUT CALIBRATION

15. ENVIRONMENTAL CONDITIONS:Operating Temperature Range: 0 to 50°CStorage Temperature Range: -40 to 80°COperating and Storage Humidity: 85% max. rela

Strona 37 - SELECT AC POWER (115/230 VAC)

20. CERTIFICATIONS AND COMPLIANCES:SAFETYIEC 1010-1, EN 61010-1: Safety requirements for electrical equipment formeasurement, control and laboratory u

Strona 38 - EMC INSTALLATION GUIDELINES

APPENDIX “C” - TROUBLESHOOTING GUIDE-41-PROBLEM POSSIBLE CAUSE REMEDIESNO DISPLAY 1. Power off, improperly connected, or brown-out. 1a. Check wiring.b

Strona 39 - A.C. Powered Basic Connection

-42-Programming of the indicator is divided into modular steps. Each module is ashort sequence of data entries. The front panel buttons “UP” and “DOWN

Strona 40

-43-“Pro 5” - PROGRAM INTEGRATOR/TOTALIZER“dECPNt”-Enter decimal point for totalizer“tbASE”-Enter time base0-second1-minute2-hour“SCLFAC”-Enter multip

Strona 41

-44-APPENDIX “E” - ORDERING INFORMATIONMODEL NO. DESCRIPTIONTOTALIZER/PEAK/VALLEYSLOPE/OFFSETE2-CONALARMOUTPUTSERIALOUTPUTANALOGOUTPUTPART NUMBERS FOR

Strona 42

LIMITED WARRANTYThe Company warrants the products it manufactures against defects in materials and work-manship for a period limited to one year from

Strona 43

IMY/IM-A 3/02DRAWING NO. LP0311Red Lion Controls 20 Willow Springs CircleYork PA 17402Tel +1 (717) 767-6511Fax +1 (717) 764-0839Red Lion Controls

Strona 44 - 12 - display hold with tare

SAFETY INFORMATIONSAFETY SUMMARYAll safety related regulations, local codes and instructions that appear inthe manual or on equipment must be observed

Strona 45

GENERAL DESCRIPTIONThe Apollo Intelligent Thermistor Meter (IMY) accepts standard Thermistorinputs and precisely linearizes them into temperature read

Strona 46

-5-Note: Analog “-” and Alarm common are separate and isolated from the signal common. The commons should NOT be tied together.BLOCK DIAGRAM*Reference

Strona 47 - LIMITED WARRANTY

PROGRAMMING AND OPERATING THE IMYPROGRAMMING THE IMYAlthough the unit has been programmed at the factory, the set-ups willgenerally have to be changed

Strona 48

DISPLAY RESULT OF “P” BUTTON“Pro” <>“0” - Causes the indicator to return to normal display mode.Any changes to set-up data are permanently store