Document Ref. XP95app.doc/Rev1 09.06.99 Page 2 of 11 Originator MC Checked by AC
1.0 Introduction
The Puissant analogue addressable control panels are designed to function with the Apollo
XP95 and Control Equipment Ltd devices listed in section 2.0 below.
NOTE 1: Some of the Apollo XP95 outstations will not function correctly with the Puissant
panels. Our own range of outstations has been designed to afford the maximum level of
flexibility for the system designer.
NOTE 2: This guide details the hardware compatible products for the Puissant panels.
The system designer should use this document in conjunction with the Puissant 1-2 loop /
1-8 loop application guides and programming guide to ensure a viable system design.
NOTE 3: We strongly recommend that an XP95 loop calculation is done for each loop as
shown in Appendix ii.
The Puissant panel allows up to 126 addresses per loop. Devices may be numbered in any
order; gaps in the numbering sequence are permitted. Isolators do not require an address
number.
1.1 Typical XP95 Loop Illustration for Puissant Panels